3000rpm Diesel Generators

  • Check oil level daily.
  • Ensure the battery is fully charged.
  • Oil change service intervals: after the first 20 hours, then every 100 hours or 12 months whichever is sooner.

Light Duty

Light duty rating is applicable for supplying power in portable and/ or intermittent applications. The average load should not be lower than 30% or higher than 80% of the rated output of the generator. Continuous use should not exceed 5 hours and annual operation should not exceed 500 hours to be within the sanctioned parameters. Emergency Duty Emergency duty rating is applicable for supplying power for the duration of a utility power outage. No overload capability is available. The average load should not be lower than 30% or higher than 80% of the rated output of the generator. The annual operation should not exceed 500 hours to be within the sanctioned parameters.

1500rpm Diesel Generators

  • Check oil and coolant levels daily.
  • Ensure the battery is fully charged.
  • Oil change service intervals 250 hours or 12 months whichever is sooner.

Prime Power

Continuous daily use. The average load should be between 30% and 80% of the rated output of the generator.

Maximum power = rated power, plus 10% for a maximum 10% duty cycle. A total lifespan in excess of 10,000 hours can be achieved with correct maintenance and use.

Emergency Duty

Emergency duty rating is applicable for supplying power for the duration of a utility power outage. Maximum power = rated power, plus 10% for a maximum 10% duty cycle.

The average load should not be lower than 30% or higher than 80% of the rated output of the generator. The annual operation should not exceed 1000 hours to be within the sanctioned parameters.